CSA-B52 Compliance Path Navigation Tool
Decision tree
Overview
Full decision path
Start: Q1
Q1 — This interactive tool will help you navigate the CSA-B52 code. By answering a series of yes/no questions, you will be able to identify sections and calculations from the code that are relevant to your application. This tool does not replace the code nor legally certify any compliance. Under no circumstances shall this tool or it's creator be liable for any direct or indirect damage or loss; physical, financial, or otherwise. Do you understand and accept these terms?
- yes → next question Q2 — Is the equipment accepted by a certification body (CSA or UL)?
- no → outcome Goodbye.
Q2 — Is the equipment accepted by a certification body (CSA or UL)?
- yes → next question Q2b — Is the ms <= 3kg (6.6lbs)?
- no → outcome Please use a certified equipment.
Q2b — Is the ms <= 3kg (6.6lbs)?
- yes → next question Q3 — Is this a packaged system?
- no → next question Q2c — Is the ms <= 10kg (22lbs)?
Q2c — Is the ms <= 10kg (22lbs)?
- yes → next question Q9 — Is this a packaged system?
- no → next question Q9c — Is the equipment with this refrigeration system located outdoors?
Q3 — Is this a packaged system?
- yes → next question Q3b — Is the system installed in a public corridor or a lobby?
- no → next question Q9c — Is the equipment with this refrigeration system located outdoors?
Q3b — Is the system installed in a public corridor or a lobby?
- yes → next question Q4 — Is the refrigerant Class A1 or B1 as per ASHRAE 34?
- no → outcome System in compliance. No EDVC calculations needed. Proceed with OEM insrtructions.
Q4 — Is the refrigerant Class A1 or B1 as per ASHRAE 34?
- yes → next question Q5 — Have you calculated the EDVC based on section 4.5.4.4?
- no → next question Q4a — Have you calculated the Ms based on section 4.5.8.3 and the EDVC based on section 4.5.4.4?
Q5 — Have you calculated the EDVC based on section 4.5.4.4?
- yes → next question Q6 — Is the ms <= EDVC?
- no → outcome Calcuations needed in order to continue.
Q4a — Have you calculated the Ms based on section 4.5.8.3 and the EDVC based on section 4.5.4.4?
- yes → next question Q8 — Is the ms <= EDVC and is the ms <= Ms, both?
- no → outcome Calcuations needed in order to continue.
Q6 — Is the ms <= EDVC?
- yes → outcome Good work! System is in compliance with the B52. System refrigerant charge is less than the EDVC or Ms value.
- no → outcome System is not in compliance with the B52. You will need to increase your installation space or change refrigerant.
Q8 — Is the ms <= EDVC and is the ms <= Ms, both?
- yes → outcome Good work! System is in compliance with the B52. System refrigerant charge is less than the EDVC or Ms value.
- no → outcome System is not in compliance with the B52. You will need to increase your installation space or change refrigerant.
Q9 — Is this a packaged system?
- yes → next question Q9b — Is the system installed in a commercial space (indoors) and not public corridor or a lobby?
- no → next question Q9c — Is the equipment with this refrigeration system located outdoors?
Q9b — Is the system installed in a commercial space (indoors) and not public corridor or a lobby?
- yes → outcome System in compliance. No EDVC calculations needed. Proceed with OEM insrtructions.
- no → next question Q9c — Is the equipment with this refrigeration system located outdoors?
Q9c — Is the equipment with this refrigeration system located outdoors?
- yes → outcome System in compliance. No EDVC calculations needed. Check section 6.2.5.6 if you have any obstruction of airflow (walls, screens, etc).
- no → next question Q10 — Is the equipment with this refrigeration system located in a lab with more than 9.3 sq. meters (100 sq. feet) per person?
Q10 — Is the equipment with this refrigeration system located in a lab with more than 9.3 sq. meters (100 sq. feet) per person?
- yes → outcome System in compliance. No EDVC calculations needed. Proceed with OEM insrtructions.
- no → next question Q10b — Is the refrigeration system located in an industrial occupancy or a refrigerated room?
Q10b — Is the refrigeration system located in an industrial occupancy or a refrigerated room?
- yes → outcome If all conditions of section 4.5.8.4 are met, the system will be in compliance. No EDVC calculations needed.
- no → next question Q11 — Is the refrigerant Class A1 or B1 as per ASHRAE 34?
Q11 — Is the refrigerant Class A1 or B1 as per ASHRAE 34?
- yes → next question Q11b — Is the system considered low-probability as per the B52 code?
- no → next question Q12 — Is the refrigerant Class A2L as per ASHRAE 34?
Q11b — Is the system considered low-probability as per the B52 code?
- yes → next question Q20 — Have you calculated the EDVC based on section 4.5.4.4?
- no → next question Q11c — Is the refrigerant class B1 as per ASHRAE 34?
Q11c — Is the refrigerant class B1 as per ASHRAE 34?
- yes → outcome System is not in compliance with the B52. A high-probability, Class B1 system is only allowed in an industrial occupancy.
- no → next question Q20 — Have you calculated the EDVC based on section 4.5.4.4?
Q12 — Is the refrigerant Class A2L as per ASHRAE 34?
- yes → next question Q12b — Is the system considered low-probability as per the B52 code?
- no → outcome Class A2, A3, B2L, B2, or B3 refrigerant noticed.
Q12b — Is the system considered low-probability as per the B52 code?
- yes → next question Q20 — Have you calculated the EDVC based on section 4.5.4.4?
- no → next question Q13 — Is the system used for human comfort?
Q13 — Is the system used for human comfort?
- yes → next question Q13b — Is there continuous or detection-based ventilation in the system/equipment?
- no → next question Q14 — Have you calculated the Ms based on section 4.5.6?
Q13b — Is there continuous or detection-based ventilation in the system/equipment?
- yes → next question Q15 — Have you calculated the EDVC based on section 4.5.5.2?
- no → next question Q16 — Have you calculated the EDVC based on section 4.5.5.3?
Q14 — Have you calculated the Ms based on section 4.5.6?
- yes → next question Q14b — Is there any indoor equipment with a capacity under 17kW (5T)?
- no → outcome Calcuations needed in order to continue.
Q15 — Have you calculated the EDVC based on section 4.5.5.2?
- yes → next question Q15b — Is there any indoor equipment with a capacity under 17kW (5T)?
- no → outcome Calcuations needed in order to continue.
Q16 — Have you calculated the EDVC based on section 4.5.5.3?
- yes → next question Q16b — Is there any indoor equipment with a capacity under 17kW (5T)?
- no → outcome Calcuations needed in order to continue.
Q14b — Is there any indoor equipment with a capacity under 17kW (5T)?
- yes → next question Q18b — Are there any release mitigation controls as per section 4.5.4.6?
- no → next question Q17b — Is the ms <= Ms (based on section 4.5.6)?
Q15b — Is there any indoor equipment with a capacity under 17kW (5T)?
- yes → next question Q18 — Are there any release mitigation controls as per section 4.5.4.6?
- no → next question Q17 — Is the ms <= EDVC (based on section 4.5.5)?
Q16b — Is there any indoor equipment with a capacity under 17kW (5T)?
- yes → next question Q18 — Are there any release mitigation controls as per section 4.5.4.6?
- no → next question Q17 — Is the ms <= EDVC (based on section 4.5.5)?
Q17 — Is the ms <= EDVC (based on section 4.5.5)?
- yes → outcome Good work! System is in compliance with the B52. System refrigerant charge is less than the EDVC or Ms value.
- no → outcome System is not in compliance with the B52. You will need to increase your installation space or change refrigerant.
Q17b — Is the ms <= Ms (based on section 4.5.6)?
- yes → outcome Good work! System is in compliance with the B52. System refrigerant charge is less than the EDVC or Ms value.
- no → outcome System is not in compliance with the B52. You will need to increase your installation space or change refrigerant.
Q18 — Are there any release mitigation controls as per section 4.5.4.6?
- yes → next question Q19 — Is the mrel <= EDVC (based on section 4.5.5)?
- no → next question Q17 — Is the ms <= EDVC (based on section 4.5.5)?
Q18b — Are there any release mitigation controls as per section 4.5.4.6?
- yes → next question Q19b — Is the mrel <= EDVC (based on section 4.5.5)?
- no → next question Q17b — Is the ms <= Ms (based on section 4.5.6)?
Q19 — Is the mrel <= EDVC (based on section 4.5.5)?
- yes → outcome Good work! System is in compliance with the B52. System refrigerant charge is less than the EDVC or Ms value.
- no → outcome System is not in compliance with the B52. You will need to increase your installation space or change refrigerant.
Q19b — Is the mrel <= EDVC (based on section 4.5.5)?
- yes → outcome Good work! System is in compliance with the B52. System refrigerant charge is less than the EDVC or Ms value.
- no → outcome System is not in compliance with the B52. You will need to increase your installation space or change refrigerant.
Q20 — Have you calculated the EDVC based on section 4.5.4.4?
- yes → next question Q20b — Is the ms <= EDVC (based on section 4.5.4.4)?
- no → outcome Calcuations needed in order to continue.
Q20b — Is the ms <= EDVC (based on section 4.5.4.4)?
Outcomes
- Goodbye.
(GOODBYE) - Reached from Q1 (no).
- Please use a certified equipment.
(CERT_NEED) - Reached from Q2 (no).
- System in compliance. No EDVC calculations needed. Proceed with OEM insrtructions.
(OK_NO_EDVC) - Reached from Q3b (no), Q9b (yes), Q10 (yes).
- System in compliance. No EDVC calculations needed. Check section 6.2.5.6 if you have any obstruction of airflow (walls, screens, etc).
(OK_OUT) - Reached from Q9c (yes).
- Calcuations needed in order to continue.
(CALC_NEED) - Reached from Q5 (no), Q4a (no), Q14 (no), Q15 (no), Q16 (no), Q20 (no).
- Good work! System is in compliance with the B52. System refrigerant charge is less than the EDVC or Ms value.
(SYS_OK) - Reached from Q6 (yes), Q8 (yes), Q17 (yes), Q17b (yes), Q19 (yes), Q19b (yes).
- System is not in compliance with the B52. You will need to increase your installation space or change refrigerant.
(NOT_OK) - Reached from Q6 (no), Q8 (no), Q17 (no), Q17b (no), Q19 (no), Q19b (no), Q20b (no).
- If all conditions of section 4.5.8.4 are met, the system will be in compliance. No EDVC calculations needed.
(OK_INDST_REF) - Reached from Q10b (yes).
- System is not in compliance with the B52. A high-probability, Class B1 system is only allowed in an industrial occupancy.
(NOT_OK_INDST) - Reached from Q11c (yes).
- Class A2, A3, B2L, B2, or B3 refrigerant noticed.
(NOT_OK_B) - Reached from Q12 (no).
- Good work! System is in compliance with the B52. System refrigerant charge is less than the EDVC. No mechanical room needed.
(OK_NO_MEC) - Reached from Q20b (yes).
Machine-Readable JSON (Canonical Model)
View JSON
{
"_meta": {
"schema": "https://www.drawdecisiontree.com/decision-dag.schema.json",
"source": "https://www.drawdecisiontree.com",
"description": "DrawDecisionTree.com is a free tool for building, sharing, and embedding interactive decision trees. This file is the machine-readable export of a published decision tree. The `dsl` field contains the original source in the Decision DAG DSL; the `dag` schema is documented at the URL in `schema` above.",
"links": {
"interactive": "https://www.drawdecisiontree.com/trees/hman/07-21-csa-b52-compliance",
"embed": "https://www.drawdecisiontree.com/embed/path/hman/07-21-csa-b52-compliance",
"dsl_reference": "https://www.drawdecisiontree.com/decision-tree-dsl-reference",
"guides": "https://www.drawdecisiontree.com/guides",
"schema_docs": "https://www.drawdecisiontree.com/decision-dag.schema.json",
"author_trees": "https://www.drawdecisiontree.com/trees/hman"
},
"generated_at": "2026-08-21T20:05:24.255Z"
},
"author": {
"handle": "hman",
"first_name": "Hemanshu",
"last_name": "Anand",
"avatar_url": "https://lh3.googleusercontent.com/a/ACg8ocKOukIj4cp2MSLESfz0C_XmSYZqIMlqONVAPWBP0gJwXYwjWv6i=s96-c",
"display_name": "Hemanshu Anand"
},
"file": {
"id": "d046d08e-0096-431e-b9e3-fc792b568b2d",
"name": "CSA-B52 Compliance Path Navigation Tool",
"public_slug": "07-21-csa-b52-compliance",
"updated_at": "2026-07-24T14:22:18.687107+00:00",
"url": "https://www.drawdecisiontree.com/trees/hman/07-21-csa-b52-compliance",
"json_url": "https://www.drawdecisiontree.com/trees/hman/07-21-csa-b52-compliance/tree.json",
"dsl_url": "https://www.drawdecisiontree.com/trees/hman/07-21-csa-b52-compliance/tree.dag"
},
"meta": {
"description": null,
"mode": "decision",
"entry": "Q1",
"tags": [],
"image": null
},
"questions": [
{
"id": "Q1",
"text": "This interactive tool will help you navigate the CSA-B52 code. By answering a series of yes/no questions, you will be able to identify sections and calculations from the code that are relevant to your application. This tool does not replace the code nor legally certify any compliance. Under no circumstances shall this tool or it's creator be liable for any direct or indirect damage or loss; physical, financial, or otherwise. Do you understand and accept these terms?"
},
{
"id": "Q2",
"text": "Is the equipment accepted by a certification body (CSA or UL)?"
},
{
"id": "Q2b",
"text": "Is the ms <= 3kg (6.6lbs)?"
},
{
"id": "Q2c",
"text": "Is the ms <= 10kg (22lbs)?"
},
{
"id": "Q3",
"text": "Is this a packaged system?"
},
{
"id": "Q3b",
"text": "Is the system installed in a public corridor or a lobby?"
},
{
"id": "Q4",
"text": "Is the refrigerant Class A1 or B1 as per ASHRAE 34?"
},
{
"id": "Q5",
"text": "Have you calculated the EDVC based on section 4.5.4.4?"
},
{
"id": "Q4a",
"text": "Have you calculated the Ms based on section 4.5.8.3 and the EDVC based on section 4.5.4.4?"
},
{
"id": "Q6",
"text": "Is the ms <= EDVC?"
},
{
"id": "Q8",
"text": "Is the ms <= EDVC and is the ms <= Ms, both?"
},
{
"id": "Q9",
"text": "Is this a packaged system?"
},
{
"id": "Q9b",
"text": "Is the system installed in a commercial space (indoors) and not public corridor or a lobby?"
},
{
"id": "Q9c",
"text": "Is the equipment with this refrigeration system located outdoors?"
},
{
"id": "Q10",
"text": "Is the equipment with this refrigeration system located in a lab with more than 9.3 sq. meters (100 sq. feet) per person?"
},
{
"id": "Q10b",
"text": "Is the refrigeration system located in an industrial occupancy or a refrigerated room?"
},
{
"id": "Q11",
"text": "Is the refrigerant Class A1 or B1 as per ASHRAE 34?"
},
{
"id": "Q11b",
"text": "Is the system considered low-probability as per the B52 code?"
},
{
"id": "Q11c",
"text": "Is the refrigerant class B1 as per ASHRAE 34?"
},
{
"id": "Q12",
"text": "Is the refrigerant Class A2L as per ASHRAE 34?"
},
{
"id": "Q12b",
"text": "Is the system considered low-probability as per the B52 code?"
},
{
"id": "Q13",
"text": "Is the system used for human comfort?"
},
{
"id": "Q13b",
"text": "Is there continuous or detection-based ventilation in the system/equipment?"
},
{
"id": "Q14",
"text": "Have you calculated the Ms based on section 4.5.6?"
},
{
"id": "Q15",
"text": "Have you calculated the EDVC based on section 4.5.5.2?"
},
{
"id": "Q16",
"text": "Have you calculated the EDVC based on section 4.5.5.3?"
},
{
"id": "Q14b",
"text": "Is there any indoor equipment with a capacity under 17kW (5T)?"
},
{
"id": "Q15b",
"text": "Is there any indoor equipment with a capacity under 17kW (5T)?"
},
{
"id": "Q16b",
"text": "Is there any indoor equipment with a capacity under 17kW (5T)?"
},
{
"id": "Q17",
"text": "Is the ms <= EDVC (based on section 4.5.5)?"
},
{
"id": "Q17b",
"text": "Is the ms <= Ms (based on section 4.5.6)?"
},
{
"id": "Q18",
"text": "Are there any release mitigation controls as per section 4.5.4.6?"
},
{
"id": "Q18b",
"text": "Are there any release mitigation controls as per section 4.5.4.6?"
},
{
"id": "Q19",
"text": "Is the mrel <= EDVC (based on section 4.5.5)?"
},
{
"id": "Q19b",
"text": "Is the mrel <= EDVC (based on section 4.5.5)?"
},
{
"id": "Q20",
"text": "Have you calculated the EDVC based on section 4.5.4.4?"
},
{
"id": "Q20b",
"text": "Is the ms <= EDVC (based on section 4.5.4.4)?"
}
],
"outcomes": [
{
"id": "GOODBYE",
"label": "Goodbye."
},
{
"id": "CERT_NEED",
"label": "Please use a certified equipment."
},
{
"id": "OK_NO_EDVC",
"label": "System in compliance. No EDVC calculations needed. Proceed with OEM insrtructions."
},
{
"id": "OK_OUT",
"label": "System in compliance. No EDVC calculations needed. Check section 6.2.5.6 if you have any obstruction of airflow (walls, screens, etc)."
},
{
"id": "CALC_NEED",
"label": "Calcuations needed in order to continue."
},
{
"id": "SYS_OK",
"label": "Good work! System is in compliance with the B52. System refrigerant charge is less than the EDVC or Ms value."
},
{
"id": "NOT_OK",
"label": "System is not in compliance with the B52. You will need to increase your installation space or change refrigerant."
},
{
"id": "OK_INDST_REF",
"label": "If all conditions of section 4.5.8.4 are met, the system will be in compliance. No EDVC calculations needed."
},
{
"id": "NOT_OK_INDST",
"label": "System is not in compliance with the B52. A high-probability, Class B1 system is only allowed in an industrial occupancy."
},
{
"id": "NOT_OK_B",
"label": "Class A2, A3, B2L, B2, or B3 refrigerant noticed."
},
{
"id": "OK_NO_MEC",
"label": "Good work! System is in compliance with the B52. System refrigerant charge is less than the EDVC. No mechanical room needed."
}
],
"dsl": "dag: CSA-B52 Compliance Path Navigation Tool\nentry: Q1\n\nQ1: This interactive tool will help you navigate the CSA-B52 code. By answering a series of yes/no questions, you will be able to identify sections and calculations from the code that are relevant to your application. This tool does not replace the code nor legally certify any compliance. Under no circumstances shall this tool or it's creator be liable for any direct or indirect damage or loss; physical, financial, or otherwise. Do you understand and accept these terms?\n hint: You may contact your Account Manager for any necessary calculations.\n yes -> Q2\n no -> [GOODBYE]\nQ2: Is the equipment accepted by a certification body (CSA or UL)?\n yes -> Q2b\n no -> [CERT_NEED]\nQ2b: Is the ms <= 3kg (6.6lbs)?\n hint: The ms is the circuit refrigerant charge, released in case of a leak.\n yes -> Q3\n no -> Q2c\nQ2c: Is the ms <= 10kg (22lbs)?\n hint: The ms is the circuit refrigerant charge, released in case of a leak.\n yes -> Q9\n no -> Q9c\nQ3: Is this a packaged system?\n hint: Not a split or a VRF system.\n yes -> Q3b\n no -> Q9c\nQ3b: Is the system installed in a public corridor or a lobby?\n yes -> Q4\n no -> [OK_NO_EDVC]\nQ4: Is the refrigerant Class A1 or B1 as per ASHRAE 34?\n yes -> Q5\n no -> Q4a\nQ5: Have you calculated the EDVC based on section 4.5.4.4?\n hint: EDVC calculation based off the RCL.\n yes -> Q6\n no -> [CALC_NEED]\nQ4a: Have you calculated the Ms based on section 4.5.8.3 and the EDVC based on section 4.5.4.4?\n hint: EDVC calculation based off the RCL; Ms calculation based off LFL.\n yes -> Q8\n no -> [CALC_NEED]\nQ6: Is the ms <= EDVC?\n yes -> [SYS_OK]\n no -> [NOT_OK]\nQ8: Is the ms <= EDVC and is the ms <= Ms, both?\n yes -> [SYS_OK]\n no -> [NOT_OK]\nQ9: Is this a packaged system?\n hint: Not a split or a VRF system.\n yes -> Q9b\n no -> Q9c\nQ9b: Is the system installed in a commercial space (indoors) and not public corridor or a lobby?\n hint: ie: shops, stores, markets, restaurants, offices, labs, etc.\n yes -> [OK_NO_EDVC]\n no -> Q9c\nQ9c: Is the equipment with this refrigeration system located outdoors?\n yes -> [OK_OUT]\n no -> Q10\nQ10: Is the equipment with this refrigeration system located in a lab with more than 9.3 sq. meters (100 sq. feet) per person?\n yes -> [OK_NO_EDVC]\n no -> Q10b\nQ10b: Is the refrigeration system located in an industrial occupancy or a refrigerated room?\n yes -> [OK_INDST_REF]\n no -> Q11\nQ11: Is the refrigerant Class A1 or B1 as per ASHRAE 34?\n yes -> Q11b\n no -> Q12\nQ11b: Is the system considered low-probability as per the B52 code?\n yes -> Q20\n no -> Q11c\nQ11c: Is the refrigerant class B1 as per ASHRAE 34?\n yes -> [NOT_OK_INDST]\n no -> Q20\nQ12: Is the refrigerant Class A2L as per ASHRAE 34?\n yes -> Q12b\n no -> [NOT_OK_B]\nQ12b: Is the system considered low-probability as per the B52 code?\n yes -> Q20\n no -> Q13\nQ13: Is the system used for human comfort?\n yes -> Q13b\n no -> Q14\nQ13b: Is there continuous or detection-based ventilation in the system/equipment?\n yes -> Q15\n no -> Q16\nQ14: Have you calculated the Ms based on section 4.5.6?\n hint: Ms calculation based off the LFL.\n yes -> Q14b\n no -> [CALC_NEED]\nQ15: Have you calculated the EDVC based on section 4.5.5.2?\n hint: EDVC calculation based off the LFL.\n yes -> Q15b\n no -> [CALC_NEED]\nQ16: Have you calculated the EDVC based on section 4.5.5.3?\n hint: EDVC calculation based off Mdef interpolation and LFL.\n yes -> Q16b\n no -> [CALC_NEED]\nQ14b: Is there any indoor equipment with a capacity under 17kW (5T)?\n hint: Such as in a split or a VRF system.\n yes -> Q18b\n no -> Q17b\nQ15b: Is there any indoor equipment with a capacity under 17kW (5T)?\n hint: Such as in a split or a VRF system.\n yes -> Q18\n no -> Q17\nQ16b: Is there any indoor equipment with a capacity under 17kW (5T)?\n hint: Such as in a split or a VRF system.\n yes -> Q18\n no -> Q17\nQ17: Is the ms <= EDVC (based on section 4.5.5)?\n yes -> [SYS_OK]\n no -> [NOT_OK]\nQ17b: Is the ms <= Ms (based on section 4.5.6)?\n yes -> [SYS_OK]\n no -> [NOT_OK]\nQ18: Are there any release mitigation controls as per section 4.5.4.6?\n hint: This gives a mrel value. Contact OEM if needed.\n yes -> Q19\n no -> Q17\nQ18b: Are there any release mitigation controls as per section 4.5.4.6?\n hint: This gives a mrel value, which replaces the ms value. Contact OEM if needed.\n yes -> Q19b\n no -> Q17b\nQ19: Is the mrel <= EDVC (based on section 4.5.5)?\n hint: The mrel value replaces the ms value. See section 4.5.4.6 and contact OEM if needed.\n yes -> [SYS_OK]\n no -> [NOT_OK]\nQ19b: Is the mrel <= EDVC (based on section 4.5.5)?\n hint: The mrel value replaces the ms value. See section 4.5.4.6 and contact OEM if needed.\n yes -> [SYS_OK]\n no -> [NOT_OK]\nQ20: Have you calculated the EDVC based on section 4.5.4.4?\n hint: EDVC calculation based off the RCL.\n yes -> Q20b\n no -> [CALC_NEED]\nQ20b: Is the ms <= EDVC (based on section 4.5.4.4)?\n yes -> [OK_NO_MEC]\n no -> [NOT_OK]\n\n[GOODBYE]: Goodbye.\n description: Please accept the terms before continuing.\n[CERT_NEED]: Please use a certified equipment.\n[OK_NO_EDVC]: System in compliance. No EDVC calculations needed. Proceed with OEM insrtructions.\n description: Results are provided for guidance only and must be verified against the current edition of CSA-B52.\n[OK_OUT]: System in compliance. No EDVC calculations needed. Check section 6.2.5.6 if you have any obstruction of airflow (walls, screens, etc).\n description: Results are provided for guidance only and must be verified against the current edition of CSA-B52.\n[CALC_NEED]: Calcuations needed in order to continue.\n description: Contact your Account Manager for help.\n[SYS_OK]: Good work! System is in compliance with the B52. System refrigerant charge is less than the EDVC or Ms value.\n description: Results are provided for guidance only and must be verified against the current edition of CSA-B52.\n[NOT_OK]: System is not in compliance with the B52. You will need to increase your installation space or change refrigerant.\n description: Results are provided for guidance only and must be verified against the current edition of CSA-B52.\n[OK_INDST_REF]: If all conditions of section 4.5.8.4 are met, the system will be in compliance. No EDVC calculations needed.\n description: Results are provided for guidance only and must be verified against the current edition of CSA-B52.\n[NOT_OK_INDST]: System is not in compliance with the B52. A high-probability, Class B1 system is only allowed in an industrial occupancy.\n description: Results are provided for guidance only and must be verified against the current edition of CSA-B52.\n[NOT_OK_B]: Class A2, A3, B2L, B2, or B3 refrigerant noticed.\n description: Please contact you Account Manager for help.\n[OK_NO_MEC]: Good work! System is in compliance with the B52. System refrigerant charge is less than the EDVC. No mechanical room needed.\n description: Results are provided for guidance only and must be verified against the current edition of CSA-B52."
}DSL Representation
dag: CSA-B52 Compliance Path Navigation Tool
entry: Q1
Q1: This interactive tool will help you navigate the CSA-B52 code. By answering a series of yes/no questions, you will be able to identify sections and calculations from the code that are relevant to your application. This tool does not replace the code nor legally certify any compliance. Under no circumstances shall this tool or it's creator be liable for any direct or indirect damage or loss; physical, financial, or otherwise. Do you understand and accept these terms?
hint: You may contact your Account Manager for any necessary calculations.
yes -> Q2
no -> [GOODBYE]
Q2: Is the equipment accepted by a certification body (CSA or UL)?
yes -> Q2b
no -> [CERT_NEED]
Q2b: Is the ms <= 3kg (6.6lbs)?
hint: The ms is the circuit refrigerant charge, released in case of a leak.
yes -> Q3
no -> Q2c
Q2c: Is the ms <= 10kg (22lbs)?
hint: The ms is the circuit refrigerant charge, released in case of a leak.
yes -> Q9
no -> Q9c
Q3: Is this a packaged system?
hint: Not a split or a VRF system.
yes -> Q3b
no -> Q9c
Q3b: Is the system installed in a public corridor or a lobby?
yes -> Q4
no -> [OK_NO_EDVC]
Q4: Is the refrigerant Class A1 or B1 as per ASHRAE 34?
yes -> Q5
no -> Q4a
Q5: Have you calculated the EDVC based on section 4.5.4.4?
hint: EDVC calculation based off the RCL.
yes -> Q6
no -> [CALC_NEED]
Q4a: Have you calculated the Ms based on section 4.5.8.3 and the EDVC based on section 4.5.4.4?
hint: EDVC calculation based off the RCL; Ms calculation based off LFL.
yes -> Q8
no -> [CALC_NEED]
Q6: Is the ms <= EDVC?
yes -> [SYS_OK]
no -> [NOT_OK]
Q8: Is the ms <= EDVC and is the ms <= Ms, both?
yes -> [SYS_OK]
no -> [NOT_OK]
Q9: Is this a packaged system?
hint: Not a split or a VRF system.
yes -> Q9b
no -> Q9c
Q9b: Is the system installed in a commercial space (indoors) and not public corridor or a lobby?
hint: ie: shops, stores, markets, restaurants, offices, labs, etc.
yes -> [OK_NO_EDVC]
no -> Q9c
Q9c: Is the equipment with this refrigeration system located outdoors?
yes -> [OK_OUT]
no -> Q10
Q10: Is the equipment with this refrigeration system located in a lab with more than 9.3 sq. meters (100 sq. feet) per person?
yes -> [OK_NO_EDVC]
no -> Q10b
Q10b: Is the refrigeration system located in an industrial occupancy or a refrigerated room?
yes -> [OK_INDST_REF]
no -> Q11
Q11: Is the refrigerant Class A1 or B1 as per ASHRAE 34?
yes -> Q11b
no -> Q12
Q11b: Is the system considered low-probability as per the B52 code?
yes -> Q20
no -> Q11c
Q11c: Is the refrigerant class B1 as per ASHRAE 34?
yes -> [NOT_OK_INDST]
no -> Q20
Q12: Is the refrigerant Class A2L as per ASHRAE 34?
yes -> Q12b
no -> [NOT_OK_B]
Q12b: Is the system considered low-probability as per the B52 code?
yes -> Q20
no -> Q13
Q13: Is the system used for human comfort?
yes -> Q13b
no -> Q14
Q13b: Is there continuous or detection-based ventilation in the system/equipment?
yes -> Q15
no -> Q16
Q14: Have you calculated the Ms based on section 4.5.6?
hint: Ms calculation based off the LFL.
yes -> Q14b
no -> [CALC_NEED]
Q15: Have you calculated the EDVC based on section 4.5.5.2?
hint: EDVC calculation based off the LFL.
yes -> Q15b
no -> [CALC_NEED]
Q16: Have you calculated the EDVC based on section 4.5.5.3?
hint: EDVC calculation based off Mdef interpolation and LFL.
yes -> Q16b
no -> [CALC_NEED]
Q14b: Is there any indoor equipment with a capacity under 17kW (5T)?
hint: Such as in a split or a VRF system.
yes -> Q18b
no -> Q17b
Q15b: Is there any indoor equipment with a capacity under 17kW (5T)?
hint: Such as in a split or a VRF system.
yes -> Q18
no -> Q17
Q16b: Is there any indoor equipment with a capacity under 17kW (5T)?
hint: Such as in a split or a VRF system.
yes -> Q18
no -> Q17
Q17: Is the ms <= EDVC (based on section 4.5.5)?
yes -> [SYS_OK]
no -> [NOT_OK]
Q17b: Is the ms <= Ms (based on section 4.5.6)?
yes -> [SYS_OK]
no -> [NOT_OK]
Q18: Are there any release mitigation controls as per section 4.5.4.6?
hint: This gives a mrel value. Contact OEM if needed.
yes -> Q19
no -> Q17
Q18b: Are there any release mitigation controls as per section 4.5.4.6?
hint: This gives a mrel value, which replaces the ms value. Contact OEM if needed.
yes -> Q19b
no -> Q17b
Q19: Is the mrel <= EDVC (based on section 4.5.5)?
hint: The mrel value replaces the ms value. See section 4.5.4.6 and contact OEM if needed.
yes -> [SYS_OK]
no -> [NOT_OK]
Q19b: Is the mrel <= EDVC (based on section 4.5.5)?
hint: The mrel value replaces the ms value. See section 4.5.4.6 and contact OEM if needed.
yes -> [SYS_OK]
no -> [NOT_OK]
Q20: Have you calculated the EDVC based on section 4.5.4.4?
hint: EDVC calculation based off the RCL.
yes -> Q20b
no -> [CALC_NEED]
Q20b: Is the ms <= EDVC (based on section 4.5.4.4)?
yes -> [OK_NO_MEC]
no -> [NOT_OK]
[GOODBYE]: Goodbye.
description: Please accept the terms before continuing.
[CERT_NEED]: Please use a certified equipment.
[OK_NO_EDVC]: System in compliance. No EDVC calculations needed. Proceed with OEM insrtructions.
description: Results are provided for guidance only and must be verified against the current edition of CSA-B52.
[OK_OUT]: System in compliance. No EDVC calculations needed. Check section 6.2.5.6 if you have any obstruction of airflow (walls, screens, etc).
description: Results are provided for guidance only and must be verified against the current edition of CSA-B52.
[CALC_NEED]: Calcuations needed in order to continue.
description: Contact your Account Manager for help.
[SYS_OK]: Good work! System is in compliance with the B52. System refrigerant charge is less than the EDVC or Ms value.
description: Results are provided for guidance only and must be verified against the current edition of CSA-B52.
[NOT_OK]: System is not in compliance with the B52. You will need to increase your installation space or change refrigerant.
description: Results are provided for guidance only and must be verified against the current edition of CSA-B52.
[OK_INDST_REF]: If all conditions of section 4.5.8.4 are met, the system will be in compliance. No EDVC calculations needed.
description: Results are provided for guidance only and must be verified against the current edition of CSA-B52.
[NOT_OK_INDST]: System is not in compliance with the B52. A high-probability, Class B1 system is only allowed in an industrial occupancy.
description: Results are provided for guidance only and must be verified against the current edition of CSA-B52.
[NOT_OK_B]: Class A2, A3, B2L, B2, or B3 refrigerant noticed.
description: Please contact you Account Manager for help.
[OK_NO_MEC]: Good work! System is in compliance with the B52. System refrigerant charge is less than the EDVC. No mechanical room needed.
description: Results are provided for guidance only and must be verified against the current edition of CSA-B52.
Machine Access
- Static JSON:
/trees/hman/07-21-csa-b52-compliance/tree.json - Live JSON (SPA):
/json/hman/07-21-csa-b52-compliance - Raw DSL:
/trees/hman/07-21-csa-b52-compliance/tree.dag - Canonical HTML:
/trees/hman/07-21-csa-b52-compliance
Questions in this decision tree
- This interactive tool will help you navigate the CSA-B52 code. By answering a series of yes/no questions, you will be able to identify sections and calculations from the code that are relevant to your application. This tool does not replace the code nor legally certify any compliance. Under no circumstances shall this tool or it's creator be liable for any direct or indirect damage or loss; physical, financial, or otherwise. Do you understand and accept these terms?
- Is the equipment accepted by a certification body (CSA or UL)?
- Is the ms <= 3kg (6.6lbs)?
- Is the ms <= 10kg (22lbs)?
- Is this a packaged system?
- Is the system installed in a public corridor or a lobby?
- Is the refrigerant Class A1 or B1 as per ASHRAE 34?
- Have you calculated the EDVC based on section 4.5.4.4?
- Have you calculated the Ms based on section 4.5.8.3 and the EDVC based on section 4.5.4.4?
- Is the ms <= EDVC?
- Is the ms <= EDVC and is the ms <= Ms, both?
- Is this a packaged system?
- Is the system installed in a commercial space (indoors) and not public corridor or a lobby?
- Is the equipment with this refrigeration system located outdoors?
- Is the equipment with this refrigeration system located in a lab with more than 9.3 sq. meters (100 sq. feet) per person?
- Is the refrigeration system located in an industrial occupancy or a refrigerated room?
- Is the refrigerant Class A1 or B1 as per ASHRAE 34?
- Is the system considered low-probability as per the B52 code?
- Is the refrigerant class B1 as per ASHRAE 34?
- Is the refrigerant Class A2L as per ASHRAE 34?
- Is the system considered low-probability as per the B52 code?
- Is the system used for human comfort?
- Is there continuous or detection-based ventilation in the system/equipment?
- Have you calculated the Ms based on section 4.5.6?
- Have you calculated the EDVC based on section 4.5.5.2?
- Have you calculated the EDVC based on section 4.5.5.3?
- Is there any indoor equipment with a capacity under 17kW (5T)?
- Is there any indoor equipment with a capacity under 17kW (5T)?
- Is there any indoor equipment with a capacity under 17kW (5T)?
- Is the ms <= EDVC (based on section 4.5.5)?
- Is the ms <= Ms (based on section 4.5.6)?
- Are there any release mitigation controls as per section 4.5.4.6?
- Are there any release mitigation controls as per section 4.5.4.6?
- Is the mrel <= EDVC (based on section 4.5.5)?
- Is the mrel <= EDVC (based on section 4.5.5)?
- Have you calculated the EDVC based on section 4.5.4.4?
- Is the ms <= EDVC (based on section 4.5.4.4)?
Possible outcomes
- Goodbye.
- Please use a certified equipment.
- System in compliance. No EDVC calculations needed. Proceed with OEM insrtructions.
- System in compliance. No EDVC calculations needed. Check section 6.2.5.6 if you have any obstruction of airflow (walls, screens, etc).
- Calcuations needed in order to continue.
- Good work! System is in compliance with the B52. System refrigerant charge is less than the EDVC or Ms value.
- System is not in compliance with the B52. You will need to increase your installation space or change refrigerant.
- If all conditions of section 4.5.8.4 are met, the system will be in compliance. No EDVC calculations needed.
- System is not in compliance with the B52. A high-probability, Class B1 system is only allowed in an industrial occupancy.
- Class A2, A3, B2L, B2, or B3 refrigerant noticed.
- Good work! System is in compliance with the B52. System refrigerant charge is less than the EDVC. No mechanical room needed.
How to use this decision tree
Click "Open interactive version" to step through the questions. Your answers narrow the tree until a recommended outcome is reached. You can also embed this tree on your own site.